ZHE JIANG BOGUANG ELECTRICAL TECHNOLOGY CO.,LTD. has been committed to product quality control and enterprise management "manufacturing high-quality goods, integrity service" is always our commitment to the customer. The company produces crystal sales of customers is the main power supply bureau, the company (hereafter called sacsc), mechanical and electrical equipment company, best-selling domestic provinces and cities autonomous regions, many times by the national key factory, export Europe and Africa southeast Asia etc, in use process to get the user high praise!
Product Overview
GGJ intelligent low voltage reactive power compensation device using computer-aided design (CAD), the introduction of the microcomputer control, the implementation of intelligent tracking the amount of reactive power compensation, reasonable structure, advanced technology, widely used in low-voltage grid, improve power factor, reduce reactive loss, improve power quality, is a new generation of energy-saving products.
Dedicated to the three-phase transformer capacity 130-600kVA reactive power compensation.
Conditions of Use
◆ Altitude: ≤2000m;
◆ Ambient temperature: -20 ℃ ~ + 45 ℃;
◆ Relative Humidity: 20 ℃ when ≤90%;
◆ Installation Environment: no harmful gases and steam, conductive or explosive dust and serious mold.
Product structural features
◆ intelligent controller, functional, reliable performance, automatic compensation; can be caused by more than 0.9 power factor improvement;
◆ Real-time display power factor, display range: Hysteresis (0.00-0.99), ahead of (0.00-0.99);
◆ with overvoltage, harmonic, over compensation, system failure, phase, and other integrated overload protection function;
◆ memory parameters have been set, the system will not be lost after a power outage parameters after power returned to normal operating status automatically, no staff on duty;
◆ according to network load balance, take or mixed phase compensation compensation;
◆ anti-interference ability can resist 2000V interference pulse amplitude input directly from the grid, higher than the national professional standards.
Can be equipped with network monitoring capabilities
◆ real-time measurement and three-phase voltage, current, frequency, active power, reactive power, power factor, active power level the whole point of a record low voltage side of the transformer, reactive power; voltage and current total harmonic distortion and 2-25 content;
◆ with RS-232 and RS-485 interface for data copying PDAs, wireless meter reading can also be achieved by remote communication capabilities, device testing, parameter settings and real-time measurement data and records data read;
◆ data analysis functions: running load data analysis and processing, statistical inquiry: a comprehensive analysis of power quality, the passing rate to calculate the voltage, power supply load rate, reliability rate and the maximum loading rate; sub-period check power factor, active and reactive power ; draw phase voltage, current, power factor and other graphs; print a comprehensive analysis and statistical reports.
Ordering Information
◆ determine the rated capacity of the transformer secondary side rated voltage, secondary current transformer ratio;
◆ determine the status and nature of reactive load power factor by electricity, and the fluctuation range is the total current compensation system work and equipment; load characteristics for the impact load, load or conventional steady-state load fluctuations;
◆ device model, type, total capacity;
◆ The equipment for outdoor box, the materials used: P steel / stainless steel and box colors:
◆ device for color indoor cabinet, device; For other distribution cabinets and counters, need to explain other distribution cabinet models, LCL way;
◆ outdoor column installation, you can install a single pole or double pole installation.
Copyright 2015 http://huifengzhiye.com All Rights Reserved Technical support:Midian